Mark Steam/Hot Water: Technical Data

            mark-model.gif (5276 bytes)

Low Speed Models

Model Mark Max. Volume (FPM) Motors (HP) Steam Heat (BTU/HR) Hot Water (BTU/HR) Steam Temp Rise (F) H.W. Temp Rise (F) Net Wt. (lb)
1-36 1,800 1/3 35,950 27,200 37 28 80
2-48 1,800 2 x 1/3 47,950 36,300 37 28 115
2-60 1,800 2 x 1/3 59,950 45,350 37 28 150
2-72 1,800 2 x 1/3 71,000 54,000 37 28 170

High Speed Models

Model Mark Max. Volume (FPM) Motors (HP) Steam Heat (BTU/HR) Hot Water (BTU/HR) Steam Temp Rise (F) H.W. Temp Rise (F) Net Wt. (lb)
1-36 2,800 1/3 51,000 34,000 30 20 80
2-48 2,800 2 x 1/3 68,000 45,400 30 20 115
2-60 2,800 2 x 1/3 85,200 56,800 30 20 150
2-72 2,800 2 x 1/3 110,000 68,000 30 20 170

Steam Rating Based on 70 degrees F entering air, 5 p.s.i. steam
Hot Water rating based on 70 degrees F. entering air, 180 degrees F entering water temp

Standard Voltages:
120 v - 1 phase 60 hz
208 v - 1 phase 60 hz
240 v - 1 phase 60 hz

Sound Level Measured 10' from unit in free field:
Low Speed - 1 motor: 51 dbA
Low Speed - 2 motors: 54 dbA
High Speed - 1 motor: 56 dbA
High Speed - 2 motors: 59 dbA

 