CIF Steam/Hot Water: Technical Data

Model CIF |
Nozzle Length |
Max. Volume (FPM) |
Max. Volume (CFM) |
Motor (s) hp |
Steam (MBTU/HR) |
Steam Temp Rise (F) |
Hot Water (MBTU/HR) |
H.W. Temp Rise (F) |
Net Wt. (lb) |
1-36 |
36 |
4,000 |
3,000 |
1 |
165 |
50 |
90 |
30 |
192 |
1-48 |
48 |
4,000 |
3,200 |
1 |
220 |
50 |
110 |
30 |
213 |
1-60 |
60 |
4,000 |
4,650 |
1 |
270 |
50 |
145 |
30 |
236 |
2-72 |
72 |
4,000 |
6,100 |
2 x 1 |
300 |
50 |
178 |
30 |
356 |
2-84 |
84 |
4,000 |
6,200 |
2 x 1 |
360 |
50 |
194 |
30 |
378 |
2-96 |
96 |
4,000 |
7,600 |
2 x 1 |
410 |
50 |
240 |
30 |
401 |
3-108 |
108 |
4,000 |
9,000 |
3 x 1 |
440 |
50 |
265 |
30 |
423 |
3-120 |
120 |
4,000 |
9,200 |
3 x 1 |
525 |
50 |
290 |
30 |
446 |
4-144 |
144 |
4,000 |
12,000 |
4 x 1 |
575 |
50 |
356 |
30 |
561 |
Standard Voltages: 115/208/230/1phase 60 hz
Sound Level Measured 10' from unit in free field: CIF, 69 dbA
Steam Rating Based on 70 degrees F entering air, 5 p.s.i. steam with a
temp rise of 45 degrees F.
Hot Water rating based on 70 degrees F. entering air, 200 degrees F entering water temp
with a temperature rise of 30 degrees F. |
Miniveil Air Systems
340 Ward St. Port Hope, ON
CANADA L1A 4A6
Telephone: 1-905-885-4015
Fax: 1-905-885-6478
Email: info@miniveil.com
|
|